The gas-fired hot water boiler is an atmospheric equipment, which means it does not need to be filed and has low risk of use. However, it is necessary to conduct a comprehensive inspection before ignition to ensure that each auxiliary engine parts are normal before watering the boiler. The following issues need to be paid attention to before watering.

1. If it is a hot water boiler larger than 2 tons, the water used must be treated to ensure that the water entering the boiler is qualified soft water, and if necessary, conduct sampling tests.

2. The feed water temperature is about 15-25 degrees, and the water supply speed should not be too fast. These are to avoid uneven heating of the boiler. Furnace workers must follow the operation manual to avoid shortening the service life.

3. After the completion of the water supply, the fireman needs to routinely check the water level of the boiler to see if the water level is abnormal. If the water level is found to drop, you need to check whether the drain valve or other valves are closed, if there is aging damage Replace with a new one immediately.

4. If the water level has reached a normal state and continues to rise, it is necessary to check whether the water pump has been turned off or whether there is a problem with the water valve. If the problem is found, please deal with it in time.


Start sequence of gas hot water boiler
⑴Start the burner, according to the burner specifications, the fuel used and the load of the gas hot water boiler, refer to the burner manual, adjust the opening of the fuel valve, and the opening of the air door in turn to achieve a good combustion state.
⑵ Set the lower limit temperature of the gas-fired hot water boiler temperature controller to 80°C, and the upper limit temperature to 95°C, so that the intermediate water in the drum rises to boiling quickly. Below 80℃, start the furnace. Above 95℃, stop the furnace.
⑶Open the inlet and outlet valves of the main coil to allow the heated medium to flow into the heat exchanger, absorb a large amount of vaporization heat, reset the upper and lower limit temperatures of the drum temperature controller, and observe whether the outlet temperature of the medium meets the requirements. Group heat exchanger, subject to the main heat exchanger), otherwise the upper and lower temperature limits can be adjusted to make the output temperature meet the design requirements. So far, the commissioning of the gas hot water boiler is completed.
⑷The normal operating pressure range of gas-fired hot water boiler is between -0.03MPa and -0.01Mpa. When the pressure is higher than -0.01Mpa, stop the furnace. When the pressure is lower than -0.03Mpa, it can be set to start the furnace automatically or not, and the furnace can be started manually.
Gas hot water boiler

The method of automatic water supply debugging for gas hot water boiler is: draw a red line 30mm above and below the center of the water level gauge, turn on the power of the electric control cabinet, put the pump switch in the manual position, and then put the pump switch in the automatic position after the water reaches the high water level. , Open the drain valve to release the water, the water level is 30 mm below the middle water level (the lower end of the pump electrode at normal water level), the pump will automatically start and automatically fill the water; close the drain valve, the water level is 30 mm above the middle water level (the lower end of the pump electrode at normal water level stop ), automatically stop the pump; then put the pump switch in the manual position, the pump starts, and the water reaches the high water level (the lower end of the high water level electrode), an alarm should be given to shut down the pump.

Get Price And Support

Related News

ABOUT US

ZOZEN is located in Wuxi,Wuxi is an important modern industrial city in China . It is only about 100 kilometers away from ShangHai.
Our products have been sold to more than 100 countries and regions and set up offices in many countries to ensure that they serve customers at the first time.

ABOUT US

ZOZEN is located in Wuxi,Wuxi is an important modern industrial city in China . It is only about 100 kilometers away from ShangHai.
Our products have been sold to more than 100 countries and regions and set up offices in many countries to ensure that they serve customers at the first time.

CONTACT US

  • +86-13915290614
  • No. 76, Xin Da Road, Zhou tie Town, Yixing, Wuxi, China